SPESIFIKASI TEKNIS
PELAKSANAAN KEGIATAN PEMELIHARAAN FIRE SUPPRESSION SYSTEM (FSS)
DATA CENTER SAWANGAN
A FIRE SUPPRESSION SYSTEM KETERANGAN
1,00 FIRE SUPPRESSION SYSTEM
Preventive Maintenance Fire Suppression Systems IG-55
LEMBAGA SANDI NEGARA - SAWANGAN DEPOK
1.1 ZONE 7 - DATA HALL 2/ SERVER ROOM AREA
MAIN EQUIPMENT
A IG55 300 BAR EQUIPMENT
- Cylinder Assembly, 80.0L IG-55 unit 58 Checking, Cleaning
- Completer Kit, Primary (c/w Solenoid) unit 2 Checking, Cleaning, Testing
- Completer Kit, Slave (c/w Pressure Gauge) unit 56 Checking, Cleaning
- Restrictor, 4" unit 1 Checking, Cleaning
- Silence Nozzle unit 30 Checking, Cleaning
- Pressure Relief Venting unit 5 Checking, Cleaning
- Discharged Pressure Switch unit 1 Checking, Cleaning
DETECTION & CONTROL SYSTEM
- Addressable Fire Control Panel c/w Battery (127 unit 1 Checking, Cleaning, Testing
addr ), FNP-1127E-R/220V* 1 loop expandable ,
- Terminal Box Fire Alarm unit 1 Checking, Cleaning
- Addressable Photoelectric Smoke Detector unit 30 Checking, Cleaning, Testing
- Manual Pull Station (Dual Action for Suppression) unit 4 Checking, Cleaning, Testing
- Suppression Abort Station c/w cover unit 4 Checking, Cleaning, Testing
- Multi-tone w/Strobe 24VDC c/w backbox unit 4 Checking, Cleaning, Testing
- Fire Alarm Bell 6" 24VDC c/w mounting unit 4 Checking, Cleaning, Testing
- Alarm Sign "Evacuate Area" (LED) unit 4 Checking, Cleaning, Testing
- Alarm Sign "Gas Discharge" (LED) unit 4 Checking, Cleaning, Testing
- Supervised Disconnect Switch unit 1 Checking, Cleaning, Testing
- Dual Input Monitor Module unit 4 Checking, Cleaning
- Supervised Output Module unit 4 Checking, Cleaning
- Dual Relay Module unit 2 Checking, Cleaning
- Supervised Output Module Release unit 1 Checking, Cleaning
- Spare Part ( Addresable Contact Input Device ) unit 1 Spare Part
1.2 ZONE 8 - MEET ME ROOM AREA
MAIN EQUIPMENT
A IG55 300 BAR EQUIPMENT
- Cylinder Assembly, 80.0L IG-55 unit 17 Checking, Cleaning
- Completer Kit, Primary (c/w Solenoid) unit 1 Checking, Cleaning, Testing
- Completer Kit, Slave (c/w Pressure Gauge) unit 16 Checking, Cleaning
- Restrictor, 4" unit 1 Checking, Cleaning
- Silence Nozzle unit 16 Checking, Cleaning
- Pressure Relief Venting unit 3 Checking, Cleaning
- Discharged Pressure Switch unit 1 Checking, Cleaning
DETECTION & CONTROL SYSTEM
- Terminal Box Fire Alarm unit 1 Checking, Cleaning
- Addressable Photoelectric Smoke Detector unit 14 Checking, Cleaning, Testing
- Manual Pull Station (Dual Action for Suppression) unit 3 Checking, Cleaning, Testing
- Suppression Abort Station c/w cover unit 3 Checking, Cleaning, Testing
- Multi-tone w/Strobe 24VDC c/w backbox unit 3 Checking, Cleaning, Testing
- Fire Alarm Bell 6" 24VDC c/w mounting unit 3 Checking, Cleaning, Testing
- Alarm Sign "Evacuate Area" (LED) unit 3 Checking, Cleaning, Testing
- Alarm Sign "Gas Discharge" (LED) unit 3 Checking, Cleaning, Testing
- Supervised Disconnect Switch unit 1 Checking, Cleaning, Testing
- Dual Input Monitor Module unit 2 Checking, Cleaning
- Supervised Output Module unit 2 Checking, Cleaning
- Dual Relay Module unit 2 Checking, Cleaning
- Supervised Output Module Release unit 1 Checking, Cleaning
1.3 ZONE 9 - UPS BATTERY ROOM B
MAIN EQUIPMENT
A IG55 300 BAR EQUIPMENT
- Cylinder Assembly, 80.0L IG-55 unit 7 Checking, Cleaning
- Completer Kit, Primary (c/w Solenoid) unit 1 Checking, Cleaning, Testing
- Completer Kit, Slave (c/w Pressure Gauge) unit 6 Checking, Cleaning
- Restrictor, 2,5" unit 1 Checking, Cleaning
- Silence Nozzle unit 4 Checking, Cleaning
- Pressure Relief Venting unit 2 Checking, Cleaning
- Discharged Pressure Switch unit 1 Checking, Cleaning
DETECTION & CONTROL SYSTEM
- Terminal Box Fire Alarm unit 1 Checking, Cleaning
- Addressable Photoelectric Smoke Detector unit 4 Checking, Cleaning, Testing
- Manual Pull Station (Dual Action for Suppression) unit 1 Checking, Cleaning, Testing
- Suppression Abort Station c/w cover unit 1 Checking, Cleaning, Testing
- Multi-tone w/Strobe 24VDC c/w backbox unit 1 Checking, Cleaning, Testing
- Fire Alarm Bell 6" 24VDC c/w mounting unit 1 Checking, Cleaning, Testing
- Alarm Sign "Evacuate Area" (LED) unit 1 Checking, Cleaning, Testing
- Alarm Sign "Gas Discharge" (LED) unit 1 Checking, Cleaning, Testing
- Supervised Disconnect Switch unit 1 Checking, Cleaning, Testing
- Dual Input Monitor Module unit 2 Checking, Cleaning
- Supervised Output Module unit 2 Checking, Cleaning
- Dual Relay Module unit 2 Checking, Cleaning
- Supervised Output Module Release unit 1 Checking, Cleaning
1.4 ZONE 10 - TRAFO MVDP ROOM B
DETECTION & CONTROL SYSTEM
- Terminal Box Fire Alarm unit 1 Checking, Cleaning
- Addressable Photoelectric Smoke Detector unit 4 Checking, Cleaning, Testing
- Dual Input Monitor Module unit 2 Checking, Cleaning
- Supervised Output Module unit 2 Checking, Cleaning
- Dual Relay Module unit 2 Checking, Cleaning
- Supervised Output Module Release unit 1 Checking, Cleaning
1.5 ZONE 11 - UMSB ROOM B
MAIN EQUIPMENT
- Terminal Box Fire Alarm unit 1 Checking, Cleaning
- Addressable Photoelectric Smoke Detector unit 4 Checking, Cleaning, Testing
- Dual Input Monitor Module unit 2 Checking, Cleaning
- Supervised Output Module unit 2 Checking, Cleaning
- Dual Relay Module unit 2 Checking, Cleaning
- Supervised Output Module Release unit 1 Checking, Cleaning
1.6 ZONE 12 - MSB ROOM B
DETECTION & CONTROL SYSTEM
- Terminal Box Fire Alarm unit 1 Checking, Cleaning
- Addressable Photoelectric Smoke Detector unit 3 Checking, Cleaning, Testing
- Dual Input Monitor Module unit 2 Checking, Cleaning
- Supervised Output Module unit 2 Checking, Cleaning
- Dual Relay Module unit 2 Checking, Cleaning
- Supervised Output Module Release unit 1 Checking, Cleaning
1.7 ZONE 13 - LVMDP ROOM B
MAIN EQUIPMENT
DETECTION & CONTROL SYSTEM
- Terminal Box Fire Alarm unit 1 Checking, Cleaning
- Addressable Photoelectric Smoke Detector unit 3 Checking, Cleaning, Testing
- Dual Input Monitor Module unit 2 Checking, Cleaning
- Supervised Output Module unit 2 Checking, Cleaning
- Dual Relay Module unit 2 Checking, Cleaning
- Supervised Output Module Release unit 1 Checking, Cleaning
1.8 ZONE 14 - GCP ROOM A
MAIN EQUIPMENT
- Terminal Box Fire Alarm unit 1 Checking, Cleaning
- Addressable Photoelectric Smoke Detector unit 3 Checking, Cleaning, Testing
- Dual Input Monitor Module unit 2 Checking, Cleaning
- Supervised Output Module unit 2 Checking, Cleaning
- Dual Relay Module unit 2 Checking, Cleaning
- Supervised Output Module Release unit 1 Checking, Cleaning
1.9 ZONE 15 - GCP ROOM B
MAIN EQUIPMENT
- Terminal Box Fire Alarm unit 1 Checking, Cleaning
- Addressable Photoelectric Smoke Detector unit 3 Checking, Cleaning, Testing
- Supervised Disconnect Switch unit 1 Checking, Cleaning
- Dual Input Monitor Module unit 2 Checking, Cleaning
- Supervised Output Module unit 2 Checking, Cleaning
- Dual Relay Module unit 2 Checking, Cleaning
- Supervised Output Module Release unit 1
1.10 ZONE 16 - MSB ROOM A
MAIN EQUIPMENT
- Terminal Box Fire Alarm unit 1 Checking, Cleaning
- Addressable Photoelectric Smoke Detector unit 2 Checking, Cleaning, Testing
- Supervised Disconnect Switch unit 1 Checking, Cleaning
- Dual Input Monitor Module unit 2 Checking, Cleaning
- Supervised Output Module unit 2 Checking, Cleaning
- Dual Relay Module unit 2 Checking, Cleaning
- Supervised Output Module Release unit 1 Checking, Cleaning
1.11 ZONE 17 - LVMDP ROOM A
MAIN EQUIPMENT
- Terminal Box Fire Alarm unit 1 Checking, Cleaning
- Addressable Photoelectric Smoke Detector unit 2 Checking, Cleaning, Testing
- Supervised Disconnect Switch unit 1 Checking, Cleaning
- Dual Input Monitor Module unit 2 Checking, Cleaning
- Supervised Output Module unit 2 Checking, Cleaning
- Dual Relay Module unit 2 Checking, Cleaning
- Supervised Output Module Release unit 1 Checking, Cleaning
1.12 ZONE 18 - MVDP ROOM A
MAIN EQUIPMENT
- Terminal Box Fire Alarm unit 1 Checking, Cleaning
- Addressable Photoelectric Smoke Detector unit 6 Checking, Cleaning, Testing
- Dual Input Monitor Module unit 2 Checking, Cleaning
- Supervised Output Module unit 2 Checking, Cleaning
- Dual Relay Module unit 2 Checking, Cleaning
- Supervised Output Module Release unit 1 Checking, Cleaning
1,13 ZONE 19 - DATA HALL 1/ SERVER ROOM AREA
MAIN EQUIPMENT
A IG55 300 BAR EQUIPMENT
- Cylinder Assembly, 80.0L IG-55 unit 14 Checking, Cleaning
- Completer Kit, Primary (c/w Solenoid) unit 1 Checking, Cleaning, Testing
- Completer Kit, Slave (c/w Pressure Gauge) unit 13 Checking, Cleaning
- Restrictor, 4" unit 1 Checking, Cleaning
- Silence Nozzle unit 6 Checking, Cleaning
- Pressure Relief Venting unit 4 Checking, Cleaning
- Discharged Pressure Switch unit 1 Checking, Cleaning
DETECTION & CONTROL SYSTEM
- Terminal Box Fire Alarm unit 1 Checking, Cleaning
- Addressable Photoelectric Smoke Detector unit 8 Checking, Cleaning, Testing
- Manual Pull Station (Dual Action for Suppression) unit 1 Checking, Cleaning, Testing
- Suppression Abort Station c/w cover unit 1 Checking, Cleaning, Testing
- Multi-tone w/Strobe 24VDC c/w backbox unit 1 Checking, Cleaning, Testing
- Fire Alarm Bell 6" 24VDC c/w mounting unit 1 Checking, Cleaning, Testing
- Alarm Sign "Evacuate Area" (LED) unit 1 Checking, Cleaning, Testing
- Alarm Sign "Gas Discharge" (LED) unit 1 Checking, Cleaning, Testing
- Supervised Disconnect Switch unit 1 Checking, Cleaning, Testing
- Dual Input Monitor Module unit 4 Checking, Cleaning
- Supervised Output Module unit 2 Checking, Cleaning
- Dual Relay Module unit 2 Checking, Cleaning
- Supervised Output Module Release unit 1 Checking, Cleaning